Scope of application
YCQ7 series magnetic starter is suitable for using in the circuits the rated voltage up to 660V, AC 50Hz or 60Hz, rated control power to 45kW and current to 95A. It is used to control the direct start and stop of the motor, and the starter with thermal overload relay protects the motor from overload and phase failure.
Standard: IEC/EN 60947-4-1.
The starter adopts a protective structure with a protective cover of IP55 and is internally composed of a CJX2 AC contactor and a JR28 thermal overload relay. The entry and exit wiring of the starter adopts the knockout type wiring hole, and the user can selectively knock and connect the four knockout holes according to the wiring requirements. The cover and the base of the starter can be completely separated, and the user is very convenient to install and maintain; the button adopts the XB2 series push button switch assembly to realize the start and stop of the starter, and it will be safe and reliable.
In order to improve the protective performance of the starter, the starter must be installed vertically. The mounting screws should be selected according to the size of the mounting hole. The screws should be no less than M5, and spring washers, flat washers and sealing rubber rings should be added to ensure the fastening of the starter. In addition, the knockout terminal holes should be equipped with corresponding waterproof terminals.